PRODUCT DETAILS

  • single1
  • single2
  • direct sealed online ups 1kva 10kva uninterruptible power supply.
  • direct sealed online ups 1kva 10kva uninterruptible power supply.
  • direct sealed online ups 1kva 10kva uninterruptible power supply.
  • direct sealed online ups 1kva 10kva uninterruptible power supply.

Direct Sealed online UPS 1KVA-10KVA Uninterruptible Power Supply

Short Description:

Place of origin: China
Type: online UPS
Model Number: BT900 1~10KVA
Display: LED
Phase: Single Phase
Waveform: pure sine wave
Transfer time: 0ms
Capacity: 1KVA 2KVA 3KVA 6KVA 10KVA
Protection: short-circuit, over voltages, reverse connection protection
OEM/ODM: Yes
Supply Ability: 10000 Piece/Pieces per Month
Packaging: Carton box package or as you requested

Product Category:

PRODUCT DETAILS

Features

  1. DSP (Digital signal processors) control;
  2. Active input power factor correction, input power factor> 0.99;
  3. Three level inverter technology, lower harmonic, higher efficiency;
  4. Wide input voltage range 55~145V and frequency range 40~70Hz;
  5. Generator compatible;
  6. Cold start function;
  7. Remote on off (ROO) function (optional);
  8. Economic operation mode (ECO);
  9. 50Hz/60Hz Frequency auto sensing;
  10. Frequency converter mode: 50Hz input / 60Hz output or 60Hz input / 50Hz output;
  11. Laser printer and ultrasound system load acceptable (customized);
  12. Communications:RS232(standard), USB / MODBUS / RS485 / SNMP / AS400 card (optional) ;
  13. Reliable design, made with strong glass fiber base (FR4) double side PCB, well designed ventilation and conformal coating.

Technical Parameters

Technical Parameters
MODEL BT901S BT901H BT902S BT902H BT903S BT903H
Capacity 1KVA/800W 2KVA/1.6KW 3KVA/2.4KW
INPUT
Input system Single phase(L/N+PE)
Norminal voltage HV:208/220/230/240/280Vac; LV:100/110/120/127Vac
Voltage range HV: 90 ~ 300Vac± 5Vac; LV: 60~145Vac± 3Vac
Frequency 40~70Hzc±0.5Hz
Power factor ≥ 0.99 @100% load
Bypass voltage range HV:115~285Vac× (1± 3%); LV:80~140Vac×(1± 3%)
OUTPUT
Output system Single phase(L/N+PE)
Output Voltage HV:208/220/230/240Vac; LV:100/110/120/127Vac
Voltage regulation ± 1%
Frequency 50/60Hz±4Hz (sync mode); 50 or 60±1%Hz (battery mode)
Waveform Pure Sine Wave THD<3% linear load; THD<6% nonlinear load
Crest factor 3:1
Harmonic distortion ≤ 2% (linear load); ≤ 5% (non-linear load)
Transfer time Mains mode to battery mode: 0ms
Inverter mode to bypass mode: 4ms (typical)
Overload capability 105% ~ 125%≥60s
125% ~ 150%≥30s
The recover point is 70%
EFFICIENCY
AC mode ≥ 92%
Battery mode ≥ 90%
ECO mode ≥ 95%
BATTERY
DC voltage 24V 36V 48V 72V 72V 96V
Inbuilt battery 2×7Ah External 4×7Ah External 6×7Ah External
Back up time 50% loaded≥ 8minutes;100%≥ loaded 3minutes(standard)
Recharge time Charger to 90% battery capacity in 5 hours(standard)Dependent on the capacity of external batteries (long backup time)
ALARMS
Utility failure 4s per beep
Low battery 1st per beep
Overload 1st per beep
UPS fault Long beep
COMMUNICATIONS
RS232 RS485 (optional) Supports Windows® 98 / 2000 / 2003 / XP / Vista / 2008 / Windows® 7 / 8 / 10
Dry contact (optional) Power manager and web browser
OTHERS
Operating temperature 0 ~ 40℃
Relative Humidity 0 ~ 90% RH(non-condensing)
Noise level <50dB
Dimensions (D×W×H) mm 282 X 145 X 220 282 X 145 X 220 397 X 145 X 220 397 X 145 X 220 421 X 190 X 318 397 X 145 X 220
Net weight (kg) 9.8 4.1 17 6.8 27.6 7.4